Parallel
Resistance
Constant Power Density
Multitrace
PVC Heating Cable:
• 3 Watts per. Foot
• Maintenance Temperature to 176º F / 80°C
• Short Term Exposure Rating (De-energized) 220º F / 105°C
• Moisture and Chemical Resistant
• Cut to Length on Site
• UL Approved
The M T PVC heating cable is a high quality, economical cable designed
for applications where minimum heat and wattage is required.
Multitrace
TPE Heating Cable:
• Watts per. foot 3, 5, 9
• Maintenance Temperature to 220° F / 105°C
• Short Term Exposure Rating (De-energized) 260º F / 127º
C
• Moisture and Chemical Resistant
• Cut to Length on Site
• UL & CSA Approved
The M-T-TPE heating cable is designed for low temperature applications
including freezers and animal pen enclosures.
Approvals: Factory Mutual Class I, Division 2, Groups B,C,D; Class II,
Division 2, Groups
E,F,G; and Class III, Division 2. (when sheath is applied)
Multitrace
FEP Heating Cable:
• Watts per. foot 3, 5, 9, 17
• Maintenance Temperature to 400º F / 204°C
• Short Term Exposure Rating (De-energized) 450º F / 232°C
• Moisture and Chemical Resistant
• Cut to Length on Site
• UL Approved
The M-T-FEP heating cable is the most commonly used cable where higher
wattage is required.
Approvals: Factory Mutual Class I, Division 2, Groups B,C,D; Class II,
Division 2, Groups
E,F,G; and Class III, Division 2. (when sheath is applied)
Multitrace
PFA Heating Cable:
• Watts per. foot 3, 5, 9, 17
• Maintenance Temperature to 450º F / 232°C
• Short Term Exposure Ratings (De-energized) 500º F / 260°C
• Moisture and Chemical Resistant
• Cut to Length on Site
• Can be Used on Steam Lines
• UL Approved
The M-T-PFA heating cable is used predominantly where high exposure temperatures
can be present. Because of the extremely high temperature capabilities
of the insulation, higher wattage is available with this cable than with
the other parallel resistant type heaters.
Approvals: Class I, Groups B,C and D Division 2 Classified areas as well
as in corrosive environments.
|